Besides not being aesthetically pleasing, what’s the downside of strictly using countertop induction cooktops, both commercial and household varieties, as my burners? If I go for the individual cooktops, I could easily replace them individually if they break or if technology or features improve, plus I can put them away for when I need more countertop space. I do use my current built in cooktop as “counter space” during gatherings, but I’m always leery of doing this for safety reasons.

Edit: There’s a wonderful community being built here. Thank you all for you responses and for the great thinking points. While I’m not entirely sure of which direction I’ll go as far as countertop vs built-in, I’m definitely sure I’ll be using induction.

  • @[email protected]
    link
    fedilink
    1011 months ago

    Depending on what kind of outlet you’re talking about and what country you’re in you may be limited in the power it will have. In the US at 110 V and maybe being able to pull 15 A (based on fuse for that circuit) you could only get 1650 W. A regular cook top or range is hard wired, has a much bigger fuse on they circuit usually 30 to 40 A and gets two phases so has 220 V which allows for much higher power output. My range’s big induction burner has 3600 W for example so it’s quite the difference.

    • JackbyDev
      link
      411 months ago

      I feel like kitchens might have 20A circuits. Regardless, I think the individual outlets are only rated 15A for the most part and I’ve never seen kitchen appliances use the 20A plug.

    • @[email protected]OP
      link
      fedilink
      311 months ago

      I’d install one 30A circuit, and one or two 20A circuit, each circuit with a single outlet.

    • orangel
      link
      fedilink
      -2
      edit-2
      11 months ago

      If your house is older, you may not be able to support multiple induction burners outright as your wiring from the power company may be insufficient. You can check by looking for a main circuit breaker in your panel. If it is only 100A, you probably cannot support induction ranges. You would have to request new wiring from your power company, then also rewire a significant amount of your in home electrical. You can still buy the desktop singular ones though.